Parameter
International default value
North American default value
Parameter 1-23 Motor Frequency
50 Hz
60 Hz
Parameter 1-25 Motor Nominal Speed
1400 RPM
1680 RPM
Parameter 1-53 Model Shift Frequency
16.7
20.0
Parameter 1-56 U/f Characteristic
50 Hz
60 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
1500 RPM
1800 RPM
Parameter 14-37 Fieldweakening Speed
1400 RPM
1680 RPM
11.4 Required Parameter Settings for Drive Options
On performing a factory reset on the drive, all drive parameters revert to their factory default value. Several drive options have pa-
rameter settings that must be congured dierently from the factory default values in order for the options to perform properly.
Table 131: Parameter Settings for the Passive Filter Option (Typecode Character 7 = P/H/L/U)
Parameter
Change value to
Parameter 5-02 Terminal 29 Mode
[1] Output
Parameter 5-10 Terminal 18 Digital Input
[7] External Interlock
Parameter 5-31 Terminal 29 Digital Output
[188] AHF Capacitor Connect
Parameter 14-51 DC-link Compensation
[0] O
Table 132: Parameter Settings for the dU/dt Filter Option (Typecode Character 18 = D/1)
Parameter
Change value to
Parameter 5-10 Terminal 18 Digital Input
[7] External Interlock
Parameter 14-52 Fan Control
[3] On 100%
(1)
1
This fan setting applies only to D9h and D10h models.
Table 133: Parameter Settings for the Sine-wave Filter Option (Typecode Character 18 = S/2)
Parameter
Change value to
Parameter 5-10 Terminal 18 Digital Input
[7] External Interlock
Parameter 14-55 Output Filter
[2] Sine-Wave Filter Fixed
Table 134: Parameter Settings for the Indicator Light + Reset Button Option (Typecode Character 28–29 = D1/DA/DB/DC/DD/DE)
Parameter
Change value to
Parameter 5-40 Function Relay [1]
[5] Running
Parameter 5-40 Function Relay [2]
[9] Alarm
Parameter 5-11 Terminal 19 Digital Input
[1] Reset
AQ357954340588en-000201 / 130R0881 | 169Danfoss A/S © 2020.09
Appendix
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N250 and is the answer not in the manual?

Danfoss VLT FC 102 N250 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N250
CategoryDC Drives
LanguageEnglish

Related product manuals