Symptom
Possible cause
Test
Solution
Terminal connection correct?
Scaling of terminals correct?
Reference signal available?
Motor running
in wrong direc-
tion
Motor rotation limit.
Check that parameter 4-10 Motor
Speed Direction is programmed cor-
rectly.
Program correct settings.
Active reversing signal.
Check if a reversing command is
programmed for the terminal in pa-
rameter group 5-1* Digital inputs.
Deactivate reversing signal.
Wrong motor phase connec-
tion.
Correct motor phase connection, or set
parameter 1-06 Clockwise Direction to
[1] Inverse.
Motor is not
reaching maxi-
mum speed
Frequency limits set wrong.
Check output limits in parameter
4-13 Motor Speed High Limit [RPM],
parameter 4-14 Motor Speed High
Limit [Hz], and parameter 4-19 Max
Output Frequency.
Program correct limits.
Reference input signal not
scaled correctly.
Check reference input signal scal-
ing in parameter group 6-0* Analog
I/O mode and parameter group 3-1*
References.
Program correct settings.
Motor speed
unstable
Possible incorrect parameter
settings.
Check the settings of all motor pa-
rameters, including all motor com-
pensation settings. For closed-loop
operation, check PID settings.
Check settings in parameter group 1-6*
Load Depen. Setting. For closed-loop
operation, check settings in parameter
group 20-0* Feedback.
Motor runs
rough
Possible overmagnetization.
Check for incorrect motor settings
in all motor parameters.
Check motor settings in parameter
groups 1-2* Motor data, 1-3* Adv Motor
Data, and 1-5* Load Indep. Setting.
Motor does not
brake
Possible incorrect settings in
the brake parameters. Ramp-
down times may be too short.
Check brake parameters. Check
ramp time settings.
Check parameter groups 2-0* DC Brake
and 3-0* Reference Limits.
Open power
fuses
Phase-to-phase short.
Motor or panel has a short phase-
to-phase. Check motor and panel
phases for shorts.
Eliminate any shorts detected.
Motor overload.
Motor is overloaded for the appli-
cation.
Perform start-up test and verify that
motor current is within specications.
If motor current is exceeding the
nameplate full load current, the motor
can run only with reduced load. Re-
view the specications for the applica-
tion.
Loose connections.
Perform pre-start-up check for
loose connections.
Tighten loose connections.
Mains current
imbalance
greater than 3%
Problem with mains power
(see Alarm 4, Mains phase loss
description).
Rotate input power leads into the
AC drive 1 position: A to B, B to C, C
to A.
If imbalanced leg follows the wire, it is
a power problem. Check the mains
supply.
AQ357954340588en-000201 / 130R0881 | 139Danfoss A/S © 2020.09
Maintenance, Diagnostics, and
Troubleshooting
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N250 and is the answer not in the manual?

Danfoss VLT FC 102 N250 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N250
CategoryDC Drives
LanguageEnglish

Related product manuals