Programmable logic controller (PLC)
Minimum 16 mm
2
(6 AWG) equalizing cable
Control cables
Minimum 200 mm (7.9 in) between control cables,
motor cables, and mains cables
Mains supply options, see IEC/EN 61800-5-1
Bare (unpainted) surface
Star washers
Brake cable (shielded) – not shown, but same
gounding principle applies as for motor cable
Motor cable (shielded)
Mains cable (unshielded)
Output contactor, and so on.
Cable insulation stripped
Common ground busbar. Follow local and national
requirements for cabinet grounding.
Brake resistor
Terminal box
Connection to motor
Motor
EMC cable gland
N O T I C E
EMC INTERFERENCE
Use shielded cables for motor and control wiring, and separate cables for input power, motor wiring, and control wiring. Failure to
isolate power, motor, and control cables can result in unintended behavior or reduced performance. Minimum 200 mm (7.9 in)
clearance is required between power, motor, and control cables.
AQ357954340588en-000201 / 130R0881 | 47Danfoss A/S © 2020.09
Electrical Installation
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N250 and is the answer not in the manual?

Danfoss VLT FC 102 N250 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N250
CategoryDC Drives
LanguageEnglish

Related product manuals