Receiving and unloading
I-beam and hooks rated to lift a drive module having a weight of 125 kg (275 lb), with the necessary safety
margins.
Crane or other lifting aid rated to lift the minimum weight specied in the documentation package supplied with
the drive module.
Crowbar to disassemble the wooden shipping container.
Installation
Drill with 10 mm or 12 mm drill bits.
Tape measurer.
Screwdriver.
Wrench with relevant metric sockets (7–17 mm).
Wrench extensions.
Torx T50 tool.
Cabinet construction
Acquire the tools necessary for assembly of the panel - according to the design plans and established practices.
4.1.2 Lifting the Unit
For measurements and center of gravity, see chapter 7.8 Kit Dimensions.
Ensure that the lifting device is suitable for the task.
Move the unit using a hoist, crane, or forklift with the appropriate rating.
Always use the dedicated lifting eye bolts. See Illustration 4.3.
CAUTION
HEAVY LOAD
Unbalanced loads can fall and loads can tip over. Failure to take proper lifting precautions increases risk of death,
serious injury, or equipment damage.
Never walk under suspended loads.
To guard against injury, wear personal protective equipment such as gloves, safety glasses, and safety shoes.
Be sure to use lifting devices with the appropriate weight rating. The lifting bar must be able to handle the
weight of the load.
The load’s center of gravity may be in an unexpected location. Failure to locate the center of gravity correctly
and position the load accordingly before lifting the load can cause the unit to fall over or tilt unexpectedly
during lifting and transport.
The angle from the top of the drive module to the lifting cables has an impact on the maximum load force on
the cable. This angle must be 65° or greater. Refer to Illustration 4.3. Attach and dimension the lifting cables
properly.
4.1.3 Storage
Store the kit in a dry location. Keep the equipment sealed in its packaging until installation. Refer to chapter 7.5 Ambient
Conditions for Drive Modules for recommended ambient conditions.
Mechanical Installation
VLT
®
Parallel Drive Modules
12 Danfoss A/S © 08/2017 All rights reserved. MG37K302
44

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals