5 Electrical Installation
5.1 Safety Instructions
See chapter 2 Safety for general safety instructions.
WARNING
INDUCED VOLTAGE
When output motor cables from dierent frequency
converters are run together, induced voltage can charge
equipment capacitors even with the equipment turned
o and locked out.
To avoid death or serious injury:
Run output motor cables separately or use
shielded cables.
Simultaneously lock out all the frequency
converters.
CAUTION
SHOCK HAZARD
The drive system can cause a DC current in the
protective earth (PE) conductor.
When a residual current-operated protective
device (RCD) is used for protection against
electrical shock, only an RCD of Type B is
allowed on the supply side.
Failure to follow this recommendation could prevent the
RCD from providing the intended protection.
NOTICE
MOTOR OVERLOAD PROTECTION
The drive modules are supplied with Class 20 overload
protection for single motor applications.
Overcurrent protection
Extra protective equipment, such as short-circuit
protection or motor thermal protection between
the drive modules and the motors, is required for
applications with multiple motors.
The correct input fusing is required to acquire
approvals and meet certication requirements,
and to provide short circuit and overcurrent
protection. These fuses are not factory-supplied,
and must be provided by the installer. See
maximum fuse ratings in chapter 7.1 Power-
dependent Specications.
Wire type and ratings
All wiring must comply with local and national
regulations regarding cross-section and ambient
temperature requirements.
Power connection wire recommendation:
minimum 75 °C rated copper wire.
See chapter 7.6 Cable Specications for recommended wire
sizes and types.
CAUTION
PROPERTY DAMAGE
Electronic thermal relay (ETR) protection against motor
overload is not included in the default setting. To
program the LCP for this function, refer to the VLT
®
Parallel Drive Modules User Guide.
Electrical Installation Installation Guide
MG37K302 Danfoss A/S © 08/2017 All rights reserved. 19
5 5

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals