7 Specications
7.1 Power-dependent Specications
7.1.1
VLT
®
HVAC Drive FC 102
Power range N315 N355 N400 N450 N500
Drive modules 2 2 2 2 2
Rectier conguration 12-pulse 6-pulse/12-pulse
High/normal load NO NO NO NO NO
Output current [A]
Continuous (at 380–440 V) 588 658 745 800 880
Intermittent (60 s overload) at 400 V 647 724 820 880 968
Continuous (at 460/500 V) 535 590 678 730 780
Intermittent (60 s overload) at 460/500 V 588 649 746 803 858
Input current [A]
Continuous (at 400 V) 567 647 733 787 875
Continuous (at 460/500 V) 516 580 667 718 759
Power losses [W]
Drive modules at 400 V 5825 6110 7069 7538 8468
Drive modules at 460 V 4998 5964 6175 6609 7140
AC bus bars at 400 V 550 555 561 565 575
AC bus bars at 460 V 548 551 556 560 563
DC bus bars during regeneration 93 95 98 101 105
Maximum cable size [mm
2
(mcm)]
Mains 4x120 (250) 4x150 (300)
Motor 4x120 (250) 4x150 (300)
Brake 4x70 (2/0) 4x95 (3/0)
Regeneration terminals
1)
4x120 (250)
4x150 (300)
6x120 (250)
Maximum external mains fuses
6-pulse conguration 600 V, 1600 A
12-pulse conguration 700 A, 600 V
Table 7.1 FC 102, 380–480 V AC Mains Supply (2-Drive System)
1) If Danfoss bus bar kit is used.
Specications Installation Guide
MG37K302 Danfoss A/S © 08/2017 All rights reserved. 45
7 7

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals