Power range N560 N630 N710 N800 N1M0
Drive modules 4 4 4 4 4
Rectier conguration 6-pulse/12-pulse
High/normal load NO NO NO NO NO
Output current [A]
Continuous (at 380–440 V) 990 1120 1260 1460 1720
Intermittent (60 s overload) at 400 V 1089 1232 1386 1606 1892
Continuous (at 460/500 V) 890 1050 1160 1380 1530
Intermittent (60 s overload) at 460/500 V 979 1155 1276 1518 1683
Input current [A]
Continuous (at 400 V) 964 1090 1227 1422 1675
Continuous (at 460/500 V) 867 1022 1129 1344 1490
Power losses [W]
Drive modules at 400 V 8810 10199 11632 13253 16463
Drive modules at 460 V 7628 9324 10375 12391 13958
AC bus bars at 400 V 665 680 695 722 762
AC bus bars at 460 V 656 671 683 710 732
DC bus bars during regeneration 218 232 250 276 318
Maximum cable size [mm
2
(mcm)]
Mains 4x185 (350) 8x120 (250)
Motor 4x185 (350) 8x120 (250)
Brake 8x70 (2/0) 8x95 (3/0)
Regeneration terminals
1)
6x120 (250) 8x120 (250) 8x150 (300) 10x150 (300)
Maximum external mains fuses
6-pulse conguration 600 V,
1600 A
600 V, 2000 A 600 V, 2500 A
12-pulse conguration 600 V, 700 A 600 V, 900 A 600 V,
1500 A
Table 7.2 FC 102, 380–480 V AC Mains Supply (4-Drive System)
1) If Danfoss bus bar kit is used.
Specications
VLT
®
Parallel Drive Modules
46 Danfoss A/S © 08/2017 All rights reserved. MG37K302