5.2 Electrical Requirements for Certications and Approvals
The standard conguration provided in this guide (drive
modules, control shelf, wire harnesses, fuses, and
microswitches) is UL and CE certied. The following
conditions must be met apart from the standard congu-
ration to obtain UL and CE regulatory approval
requirements. For a list of disclaimers, see
chapter 8.1 Disclaimer.
Use the frequency converter in a heated, indoor-
controlled environment. Cooling air must be
clean, free from corrosive materials, and
electrically conductive dust. See for specic limits.
Maximum ambient air temperature is 40 °C
(104 °F) at rated current.
The drive system must be assembled in clean air,
according to enclosure classication. To obtain UL
or CE certication regulatory approvals, drive
modules must be installed according to the
standard conguration provided in this guide.
Maximum voltage and current must not exceed
the values provided in chapter 7.1 Power-
dependent
Specications for the specied drive
conguration.
The drive modules are suitable for use on a
circuit capable of delivering not more than
100 kA rms symmetrical amperes at the drive
nominal voltage (600 V maximum for 690 V units)
when protected by fuses with the standard
conguration. Refer to chapter 5.4.1 Fuse Selection.
The ampere rating is based on tests done
according to UL 508C.
The cables located within the motor circuit must
be rated for at least 75 °C (167 °F) in UL-
compliant installations. The cable sizes have been
provided in chapter 7.1 Power-dependent Speci-
cations for the specied drive conguration.
The input cable must be protected with fuses.
Circuit breakers must not be used without fuses
in the U.S. Suitable IEC (class aR) fuses and UL
(class L or T) fuses are listed in chapter 5.4.1 Fuse
Selection. In addition, country-specic regulatory
requirements must be adhered to.
For installation in the U.S., branch circuit
protection must be provided according to the
National Electrical Code (NEC) and any applicable
local codes. To fulll this requirement, use UL-
classied fuses.
For installation in Canada, branch circuit
protection must be provided according to the
Canadian Electrical Code and any applicable
provincial codes. To fulll this requirement, use
the UL-classied fuses.
Electrical Installation
VLT
®
Parallel Drive Modules
20 Danfoss A/S © 08/2017 All rights reserved. MG37K302
55

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals