Control card, RS-485 serial communication
Terminal number 68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number 61 Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs 2
Terminal number 27, 29
1)
Voltage level at digital/frequency output 0–24 V
Max. output current (sink or source) 40 mA
1) Terminal 27 and 29 can also be programmed as input.
Control card, 24 V DC output
Terminal number 13
Max. load 200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Surroundings
Enclosure IP21, IP54
Vibration test 1.0 g
Relative humidity 5% - 95% (IEC 721-3-3; class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class kD
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature
- with derating maximum 50 °C
- at full continuous output current max. 40 °C
Minimum ambient temperature -10 °C
Temperature during storage/transport -25 to +65 °C
Maximum altitude above sea level without derating 1000 m
Maximum altitude above sea level with derating 3000 m
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Control card performance
Scan interval 5 ms
Control card, USB serial communication
USB standard 1.1 (full speed)
USB plug USB type B “device” plug
Generic specifications
Maximum parallel filters 4 on same CT set
Filter efficiency 97%
Typical average switching frequency 3.0–4.5 kHz
Response time (reactive and harmonic) < 0.5 ms
Settling time - reactive current control < 20 ms
Settling time - harmonic current control < 20 ms
Overshoot reactive current control <10%
Overshoot Harmonic current control <10%
Specifications Operating Instructions
MG37A202 Danfoss A/S © Rev. 2014-07-29 All rights reserved. 151
11 11

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302
CategoryController
LanguageEnglish

Related product manuals