EasyManuals Logo
Home>Danfoss>Controller>VLT FC 302

Danfoss VLT FC 302 User Manual

Danfoss VLT FC 302
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
3.4.11 Mains Disconnects
Frame size Power & Voltage Type
D P132-P200 380–500 V OT400U12-9 or ABB OETL-NF400A
E P250 380-500 V ABB OETL-NF600A
E P315-P400 380-500 V ABB OETL-NF800A
F P450 380-500 V Merlin Gerin NPJF36000S12AAYP
F P500-P630 380-500 V Merlin Gerin NRK36000S20AAYP
Table 3.9 Recommended Mains Disconnects
3.4.12 F-Frame Circuit Breakers
Frame size Power & Voltage Type
F P450 380-500 V Merlin Gerin NPJF36120U31AABSCYP
F P500-P630 380-500 V Merlin Gerin NRJF36200U31AABSCYP
Table 3.10 Recommended Circuit Breakers
3.4.13 F-Frame Mains Contactors
Frame size Power & Voltage Type
F P450-P500 380-500 V Eaton XTCE650N22A
F P560-P630 380-500 V Eaton XTCEC14P22B
Table 3.11 Recommended Contactors
3.4.14 Motor Insulation
For motor cable lengths the maximum cable length, the
motor insulation ratings listed in Table 3.12 are
recommended. The peak voltage can be twice the DC-link
voltage or 2.8 times mains voltage, due to transmission
line effects in the motor cable. If a motor has lower
insulation rating, use a dU/dt or sine wave filter.
Nominal Mains Voltage Motor Insulation
U
N
420 V
Standard U
LL
= 1,300 V
420 V < U
N
500 V Reinforced U
LL
= 1,600 V
Table 3.12 Recommended Motor Insulation Ratings
3.4.15
Motor Bearing Currents
Motors with a rating 110 kW or higher combined with
frequency converters are best with NDE (Non-Drive End)
insulated bearings to eliminate circulating bearing currents
caused by motor size. To minimise DE (Drive End) bearing
and shaft currents, proper grounding is required for:
Frequency converter
Motor
Motor-driven machine
Motor to the driven machine
Although failure due to bearing currents is infrequent, use
the following strategies to reduce the likelihood:
Use an insulated bearing
Apply rigorous installation procedures
Ensure that the motor and load motor are
aligned
Strictly follow the EMC Installation guideline
Reinforce the PE so the high frequency
impedance is lower in the PE than the input
power leads
Provide a good high frequency connection
between the motor and the frequency converter
Ensure that the impedance from frequency
converter to building ground is lower than the
grounding impedance of the machine. Make a
direct ground connection between the motor and
load motor.
Apply conductive lubrication
Try to ensure that the line voltage is balanced to
ground.
Use an insulated bearing as recommended by the
motor manufacturer (note: Motors from reputable
manufacturers typically have insulated bearings
as standard in motors of this size)
Installation Operating Instructions
MG37A202 Danfoss A/S © Rev. 2014-07-29 All rights reserved. 29
3 3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302
CategoryController
LanguageEnglish

Related product manuals