6 Programming
6.1 How to Programme the Frequency
Converter
6.1.1 Quick Setup Parameters
0-01 Language
Option: Function:
Defines the language to be used in the
display. The frequency converter can be
delivered with 4 different language
packages. English and German are
included in all packages. English cannot be
erased or manipulated.
[0] * English Part of Language packages 1 - 4
[1] Deutsch Part of Language packages 1 - 4
[2] Francais Part of Language package 1
[3] Dansk Part of Language package 1
[4] Spanish Part of Language package 1
[5] Italiano Part of Language package 1
[6] Svenska Part of Language package 1
[7] Nederlands Part of Language package 1
[10] Chinese Part of Language package 2
[20] Suomi Part of Language package 1
[22] English US Part of Language package 4
[27] Greek Part of Language package 4
[28] Bras.port Part of Language package 4
[36] Slovenian Part of Language package 3
[39] Korean Part of Language package 2
[40] Japanese Part of Language package 2
[41] Turkish Part of Language package 4
[42] Trad.Chinese Part of Language package 2
[43] Bulgarian Part of Language package 3
[44] Srpski Part of Language package 3
[45] Romanian Part of Language package 3
[46] Magyar Part of Language package 3
[47] Czech Part of Language package 3
[48] Polski Part of Language package 4
[49] Russian Part of Language package 3
0-01 Language
Option: Function:
[50] Thai Part of Language package 2
[51] Bahasa
Indonesia
Part of Language package 2
1-20 Motor Power [kW]
Range: Function:
4.00
kW*
[0.09 -
3000.00
kW]
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while
the motor is running. This parameter is
visible in LCP if 0-03 Regional Settings is [0]
International .
NOTICE
Four sizes down, one size up from
nominal unit rating.
1-22 Motor Voltage
Range: Function:
Size
related*
[ 10 -
1000 V]
Enter the nominal motor voltage
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while
the motor is running.
1-23 Motor Frequency
Range: Function:
50.
Hz*
[20 -
1000
Hz]
Min - Max motor frequency: 20 - 1000Hz.
Select the motor frequency value from the
motor nameplate data. If a value different from
50 Hz or 60 Hz is selected, it is necessary to
adapt the load independent settings in
1-50 Motor Magnetisation at Zero Speed to
1-53 Model Shift Frequency. For 87 Hz operation
with 230/400 V motors, set the nameplate data
for 230V/50 Hz. Adapt 4-13 Motor Speed High
Limit [RPM] and parameter 3-03 Maximum
Reference to the 87 Hz application.
1-24 Motor Current
Range: Function:
Size
related*
[ 0.10 -
10000.00 A]
Enter the nominal motor current
value from the motor nameplate
data. This data is used for
calculating motor torque, motor
thermal protection etc.
Programming Operating Instructions
MG37A202 Danfoss A/S © Rev. 2014-07-29 All rights reserved. 49