EasyManuals Logo
Home>Danfoss>Controller>VLT FC 302

Danfoss VLT FC 302 User Manual

Danfoss VLT FC 302
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #144 background imageLoading...
Page #144 background image
11.1.2 Derating for Temperature
The frequency converter automatically derates the
switching frequency, switching type, or output current
under certain load or ambient conditions as described
below. The derating curves in Illustration 11.1 and
Illustration 11.2 apply to both SFAVM and 60 AVM
switching modes.
130BX491.10
Iout [%]
fsw
[kHz]
o
70
80
90
0.5
60
100
110
2.0
50 C
55 C
0.0
o
1.0 1.5 2.5 4.03.0 3.5
o
45 C
Illustration 11.1 Derating Frame Sizes D, E, and F 380-500 V
(T5) High Overload 150%
130BX492.10
o
70
80
90
0.5
Iout [%]
60
100
110
2.0
fsw
[kHz]
50 C
55 C
0.0
o
1.0 1.5 2.5 4.03.0 3.5
o
45 C
o
40 C
50
Illustration 11.2 Derating Frame Sizes D, E, and F 380-500 V
(T5) Normal Overload 110%
Specifications Operating Instructions
142 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202
1111

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302
CategoryController
LanguageEnglish

Related product manuals