EasyManuals Logo
Home>Danfoss>Controller>VLT FC 302

Danfoss VLT FC 302 User Manual

Danfoss VLT FC 302
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #156 background imageLoading...
Page #156 background image
11.5.2 Fuse Tables
UL Compliance Fuse tables
380-480 V, frame sizes D, E and F
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or 500 V,
or 600 V depending on the frequency converter voltage rating. With the proper fusing the frequency converter Short Circuit
Current Rating (SCCR) is 100,000 Arms.
Size/
Type
Bussmann
E1958
JFHR2**
Bussmann
E4273
T/JDDZ**
SIBA
E180276
JFHR2
LittelFuse
E71611
JFHR2**
Ferraz-
Shawmut
E60314
JFHR2**
Bussmann
E4274
H/JDDZ**
Bussmann
E125085
JFHR2*
Internal
Option
Bussmann
P132 FWH-
400
JJS-
400
2061032.40 L50S-400 A50-P400 NOS-
400
170M4012 170M4016
P160 FWH-
500
JJS-
500
2061032.50 L50S-500 A50-P500 NOS-
500
170M4014 170M4016
P200 FWH-
600
JJS-
600
2062032.63 L50S-600 A50-P600 NOS-
600
170M4016 170M4016
Table 11.6 Frame size D, Line Fuses, 380-480 V
Size/Type Bussmann PN* Rating Ferraz Siba
P250 170M4017 700 A, 700 V 6.9URD33D08A0700 20 630 32.700
P315 170M6013 900 A, 700 V 6.9URD33D08A0900 20 630 32.900
P355 170M6013 900 A, 700 V 6.9URD33D08A0900 20 630 32.900
P400 170M6013 900 A, 700 V 6.9URD33D08A0900 20 630 32.900
Table 11.7 Frame size E, Line Fuses, 380-480 V
Size/Type Bussmann PN* Rating Siba
Internal Bussmann
Option
P450 170M7081 1600 A, 700 V 20 695 32.1600 170M7082
P500 170M7081 1600 A, 700 V 20 695 32.1600 170M7082
P560 170M7082 2000 A, 700 V 20 695 32.2000 170M7082
P630 170M7082 2000 A, 700 V 20 695 32.2000 170M7082
Table 11.8 Frame size F, Line Fuses, 380-480 V
Size/Type Bussmann PN* Rating Siba
P450 170M8611 1100 A, 1000 V 20 781 32.1000
P500 170M8611 1100 A, 1000 V 20 781 32.1000
P560 170M6467 1400 A, 700 V 20 681 32.1400
P630 170M6467 1400 A, 700 V 20 681 32.1400
Table 11.9 Frame Size F, Inverter Module DC Link Fuses, 380-480 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and
amperage may be substituted for external use
**Any minimum 500 V UL listed fuse with associated current rating may be used to meet UL requirements.
11.5.3
Supplementary Fuses - High Power
Supplementary fuses
Frame size Bussmann PN Rating
D, E and F KTK-4 4 A, 600 V
Table 11.10 SMPS Fuse
Specifications Operating Instructions
154 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202
1111