Illustration 5.10 Info Key
Navigation keys
The 4 navigation keys are used to navigate between the
choices available in [Quick Menu], [Main Menu] and
[Alarm Log]. Move the cursor with the navigation keys.
[OK]
is used for selecting a parameter marked by the cursor and
for enabling the change of a parameter.
130BT117.10
OK
Back
Info
Warn
Alarm
On
Cancel
Illustration 5.11 Navigation Keys
Operation keys
For local control. Found at the bottom of the control
panel.
130BP046.10
Hand
on
O
Auto
on
Reset
Illustration 5.12 Operation Keys
[Hand On]
enables control of the frequency converter via the GLCP.
[Hand On] also starts the motor, and it is now possible to
give the motor speed reference with the arrow keys. The
key can be [1] Enabled or [0] Disabled via 0-40 [Hand on]
Key on LCP.
The following control signals are active when [Hand On]
is activated:
[Hand On] - [Off] - [Auto On]
Reset
Coasting stop inverse (motor coasting to stop)
Reversing
Set-up select lsb - Set-up select msb
Stop command from serial communication
Quick stop
DC brake
NOTICE
External stop signals activated with control signals or a
serial bus overrides a “start” command via the LCP.
[Off]
stops the connected motor (when pressed on the
frequency converter LCP) or the filter (when pressed on
the filter LCP). The key can be [1] Enabled or [0] Disabled
via 0-41 [Off] Key on LCP. If no external stop function is
selected and the [Off] key is inactive, the motor can only
be stopped by disconnecting the mains supply.
[Auto On]
enables the frequency converter to be controlled via the
control terminals and/or serial communication. When a
start signal is applied on the control terminals and/or the
bus, the frequency converter starts. The key can be [1]
Enabled or [0] Disabled via 0-42 [Auto on] Key on LCP.
NOTICE
An active HAND-OFF-AUTO signal via the digital inputs
has higher priority than the control keys [Hand On]
[Auto On].
[Reset]
Is used for resetting the frequency converter or filter after
an alarm (trip). The key can be [1] Enabled or [0] Disabled
via 0-43 [Reset] Key on LCP on the LCP. Reset
The parameter shortcut
can be carried out by holding down the [Main Menu] key
for 3 seconds. The parameter shortcut allows direct access
to any parameter.
5.1.3
Changing Data
1. Press [Quick Menu] or [Main Menu].
2.
Use [
] and [
] to find parameter group to edit.
Changing data
3. Press [OK].
4.
Use [
] and [
] to find parameter to edit.
5. Press [OK].
6.
Use [
] and [
] to select correct parameter
setting. Or, to move to digits within a number,
use [] and []. Cursor indicates digit selected to
change. [
] key increases the value, [
] key
decreases the value.
7. Press [Cancel] to ignore the change, or press [OK]
to accept the change and enter a new setting.
User Interface
Operating Instructions
MG37A202 Danfoss A/S © Rev. 2014-07-29 All rights reserved. 45
5 5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302
CategoryController
LanguageEnglish

Related product manuals