5-01 Terminal 27 Mode
Option: Function:
NOTICE
This parameter cannot be adjusted while the
motor is running.
[0] Input Defines terminal 27 as a digital input.
[1] Output Defines terminal 27 as a digital output.
5-02 Terminal 29 Mode
Option: Function:
This parameter is available for FC 302 only.
[0] * Input Defines terminal 29 as a digital input.
[1] Output Defines terminal 29 as a digital output.
6.1.4 Digital Inputs
The digital inputs are used for selecting various functions
in the frequency converter. All digital inputs can be set to
the following functions:
Digital input function Select Terminal
No operation [0] All *term 32, 33
Reset [1] All
Coast inverse [2] All *term 27
Coast and reset inverse [3] All
Quick stop inverse [4] All
DC-brake inverse [5] All
Stop inverse [6] All
Start [8] All *term 18
Latched start [9] All
Reversing [10] All *term 19
Start reversing [11] All
Enable start forward [12] All
Enable start reverse [13] All
Jog [14] All *term 29
Preset reference on [15] All
Preset ref bit 0 [16] All
Preset ref bit 1 [17] All
Preset ref bit 2 [18] All
Freeze reference [19] All
Freeze output [20] All
Speed up [21] All
Speed down [22] All
Set-up select bit 0 [23] All
Set-up select bit 1 [24] All
Precise stop inverse [26] 18, 19
Precise start, stop [27] 18, 19
Catch up [28] All
Slow down [29] All
Counter input [30] 29, 33
Pulse input ddge trigged [31] 29, 33
Digital input function Select Terminal
Pulse input time based [32] 29, 33
Ramp bit 0 [34] All
Ramp bit 1 [35] All
Latched precise start [40] 18, 19
Latched precise stop
inverse
[41] 18, 19
External interlock [51]
DigiPot increase [55] All
DigiPot decrease [56] All
DigiPot clear [57] All
Digipot hoist [58] All
Counter A (up) [60] 29, 33
Counter A (down) [61] 29, 33
Reset Counter A [62] All
Counter B (up) [63] 29, 33
Counter B (down) [64] 29, 33
Reset counter B [65] All
Mech. brake feedb. [70] All
Mech. brake feedb. inv. [71] All
PID error inv. [72] All
PID reset I-part [73] All
PID enable [74] All
PTC card 1 [80] All
Profidrive OFF2 [91]
Profidrive OFF3 [92]
Start edge triggered [98]
Safe option reset [100]
Table 6.5 Digital Input Functions
FC 300 standard terminals are 18, 19, 27, 29, 32 and 33.
MCB 101 terminals are X30/2, X30/3 and X30/4.
Terminal 29 functions as an output only in FC 302.
Functions dedicated to only one digital input are stated in
the associated parameter.
All digital inputs can be programmed to these functions:
[0]
No
operation
No reaction to signals transmitted to the
terminal.
[1] Reset Resets frequency converter after a TRIP/
ALARM. Not all alarms can be reset.
[2] Coast
inverse
(Default digital input 27): Coasting stop,
inverted input (NC). The frequency converter
leaves the motor in free mode. Logic ‘0’ ⇒
coasting stop.
[3] Coast and
reset
inverse
Reset and coasting stop Inverted input (NC).
Leaves motor in free mode and resets
frequency converter. Logic ‘0’ ⇒ coasting stop
and reset.
[4] Quick stop
inverse
Inverted input (NC). Generates a stop in
accordance with quick-stop ramp time set in
3-81 Quick Stop Ramp Time. When motor stops,
Programming Operating Instructions
MG37A202 Danfoss A/S © Rev. 2014-07-29 All rights reserved. 61
6 6