6.3.10 8-** Comm. and Options
Par. No. # Parameter description Default value 4-set-up FC 302
only
Change
during
operation
Conver-
sion
index
Type
8-0* General Settings
8-01 Control site
[0] Digital and
ctrl.word All set-ups TRUE - Uint8
8-02 Control word source null All set-ups TRUE - Uint8
8-03 Control word timeout time 1.0 s 1 set-up TRUE -1 Uint32
8-04 Control word timeout function null 1 set-up TRUE - Uint8
8-05 End-of-timeout function [1] Resume set-up 1 set-up TRUE - Uint8
8-06 Reset control word timeout [0] Do not reset All set-ups TRUE - Uint8
8-07 Diagnosis trigger [0] Disable 2 set-ups TRUE - Uint8
8-08 Readout filtering null All set-ups TRUE - Uint8
8-1* Ctrl. Word Settings
8-10 Control word profile [0] FC profile All set-ups TRUE - Uint8
8-13 Configurable status word STW null All set-ups TRUE - Uint8
8-14 Configurable control word CTW [1] Profile default All set-ups TRUE - Uint8
8-3* FC Port Settings
8-30 Protocol [0] FC 1 set-up TRUE - Uint8
8-31 Address 1 N/A 1 set-up TRUE 0 Uint8
8-32 FC port baud rate null 1 set-up TRUE - Uint8
8-33 Parity/stop bits
[0] Even Parity, 1 Stop
Bit 1 set-up TRUE - Uint8
8-34 Estimated cycle time 0 ms 2 set-ups TRUE -3 Uint32
8-35 Minimum response delay 10 ms All set-ups TRUE -3 Uint16
8-36 Max response delay App.Dependent 1 set-up TRUE -3 Uint16
8-37 Max inter-char delay App.Dependent 1 set-up TRUE -5 Uint16
8-4* FC MC protocol set
8-40 Telegram selection
[1] Standard telegram
1 2 set-ups TRUE - Uint8
8-41 Parameters for signals 0 All set-ups FALSE - Uint16
8-42 PCD write configuration App.Dependent All set-ups TRUE - Uint16
8-43 PCD read configuration App.Dependent All set-ups TRUE - Uint16
8-5* Digital/Bus
8-50 Coasting select [3] Logic OR All set-ups TRUE - Uint8
8-51 Quick stop select [3] Logic OR All set-ups TRUE - Uint8
8-52 DC brake select [3] Logic OR All set-ups TRUE - Uint8
8-53 Start select [3] Logic OR All set-ups TRUE - Uint8
8-54 Reversing select [3] Logic OR All set-ups TRUE - Uint8
8-55 Set-up select [3] Logic OR All set-ups TRUE - Uint8
8-56 Preset reference select [3] Logic OR All set-ups TRUE - Uint8
8-57 Profidrive OFF2 select [3] Logic OR All set-ups TRUE - Uint8
8-58 Profidrive OFF3 select [3] Logic OR All set-ups TRUE - Uint8
8-8* FC Port Diagnostics
8-80 Bus message count 0 N/A All set-ups TRUE 0 Uint32
8-81 Bus error count 0 N/A All set-ups TRUE 0 Uint32
8-82 Slave messages rcvd 0 N/A All set-ups TRUE 0 Uint32
8-83 Slave error count 0 N/A All set-ups TRUE 0 Uint32
8-9* Bus Jog
8-90 Bus jog 1 speed 100 RPM All set-ups TRUE 67 Uint16
8-91 Bus jog 2 speed App.Dependent All set-ups TRUE 67 Uint16
Programming Operating Instructions
86 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202
66

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302
CategoryController
LanguageEnglish

Related product manuals