5.1.17 24-** Appl. Functions 2
Par.
No. #
Parameter description Default value 2-set-up Change
during
operation
Conversion
index
Type
24-0* Fire Mode
24-00 FM Function [0] Disabled 1 set-up FALSE – Uint8
24-01 Fire Mode Conguration [0] Open Loop All set-ups FALSE – Uint8
24-05 FM Preset Reference 0% All set-ups TRUE 0 Int16
24-06 Fire Mode Reference Source [0] No function All set-ups FALSE – Uint8
24-07 Fire Mode Feedback Source [0] No function All set-ups FALSE – Uint8
24-09 FM Alarm Handling [1] Trip, Crit.Alarms 1 set-up FALSE – Uint8
24-1* Drive Bypass
24-10 Drive Bypass Function [0] Disabled 1 set-up FALSE – Uint8
24-11 Drive Bypass Delay Time 0 s 1 set-up FALSE 0 Uint16
5.1.18 30-** Special Features
Par.
No. #
Parameter description Default value 2-set-up Change during
operation
Conversion
index
Type
30-2* Adv. Start Adjust
30-22 Locked Rotor Detection [0] O All set-ups FALSE - Uint8
30-23 Locked Rotor Detection Time [s] 0.10 s All set-ups FALSE -2 Uint8
Parameter Lists Programming Guide
MG18B502 Danfoss A/S © 04/2018 All rights reserved. 117