3.11 Main Menu - Drive Information - Group
15
Parameter group containing frequency converter
information such as operating data, hardware congu-
ration, and software versions.
3.11.1 15-0* Operating Data
15-00 Operating hours
Range: Function:
0 h* [0 - 0x7f. h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is turned
o.
15-01 Running Hours
Range: Function:
0 h* [0 -
0x7f. h]
View how many hours the motor has run.
Reset the counter in parameter 15-07 Reset
Running Hours Counter. The value is saved
when the frequency converter is turned o.
15-02 kWh Counter
Range: Function:
0 kWh* [0 - 65535
kWh]
View the output power of the frequency
converter in kWh as a mean value over 1
hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0* [0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range: Function:
0* [0 - 65535 ] View the number of frequency converter
temperature faults that have occurred.
15-05 Over Volt's
Range: Function:
0* [0 - 65535 ] View the number of frequency converter
overvoltages that have occurred.
15-06 Reset kWh Counter
Option: Function:
NOTICE
To reset, press [OK].
[0] * Do not reset
15-06 Reset kWh Counter
Option: Function:
[1] Reset counter To reset the kWh counter to 0, select [1]
Reset and press [OK] (see
parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset
[1] Reset counter To reset the running hours counter, select [1]
Reset counter and press [OK]
(parameter 15-01 Running Hours) to 0 (see
also parameter 15-01 Running Hours).
3.11.2 15-3* Alarm Log
Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] the oldest. Fault codes, values, and time
stamp can be viewed for all logged data.
15-30 Alarm Log: Error Code
Range: Function:
0* [0 - 255 ] View the fault code and lookup its meaning in
chapter 4 Troubleshooting.
15-31 InternalFaultReason
Range: Function:
0* [-32767 - 32767 ] View a description of the error. This
parameter is used with alarm 38, Internal
Fault.
3.11.3 15-4* Drive Identication
Parameters containing read-only information about the
hardware and software conguration of the frequency
converter.
15-40 FC Type
Range: Function:
0* [0 - 6 ] View the FC type code. The readout is identical to
the frequency converter series power eld of the
type code denition, characters 1–6.
15-41 Power Section
Range: Function:
0* [0 - 20 ] View the FC type code. The readout is identical to
the frequency converter series power eld of the
type code denition, characters 7–10.
Parameters Programming Guide
MG18B502 Danfoss A/S © 04/2018 All rights reserved. 79
3 3

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals