Chapter 3 : Installation
12
3.3. EnviroProbe
Detecting environment temperature and humidity, the EnviroProbes are designed to
work with the EnviroStation. You can cascade multiple EnviroProbes to extend the
detecting range. To install the EnviroProbe(s), please see the following instructions.
Step 1 Set the Comm DIP switch to Station on the EnviroProbe(s).
Step 2 Make sure the last EnviroProbe in the chain (the farthest) is set to Rt-Yes,
and the rest of the EnviroProbes are set to Rt-No. If only one EnviroProbe
is connected, please also make sure that it is set to Rt-Yes.
Step 3 Set the ID DIP switch to assign an ID for each EnviroProbe (please refer to
the EnviroProbe User Manual). No particular numeric order is required for
the connected units; however, make sure that each EnviroProbe is
assigned with a unique ID. Up to ten EnviroProbes can be cascaded.
Step 4 Attach the EnviroProbe(s) to rack cabinet doors or metal plates.
Step 5 Use a standard CAT5 cable to connect the first (nearest) EnviroProbe’s
Input to the Delta-BUS port on the rear panel.
Step 6 Cascade other EnviroProbes using standard CAT5 cables. Connect the
Output port to the next EnviroProbe’s Input port. Please see the figure
below.