Appendix A : Specifications
78
Appendix A : Specifications
Model Part no.
Item
EMS2000 EMS2000000
Input
Power Input 100 ~ 240 Vac, 1.2A, 50/60 Hz
Wet Contact signal
Alarm Voltage:5 ~ 24 Vdc
Dry Contact signal
Normal: Off (open circuit)
Digital Input
Alarm: On (short circuit)
Input Voltage: 0 ~ 10V
Analog Input
Input Current: 0 ~ 20 mA
Range: 0 ~ 50°C
RTD
Accuracy: ± 1°C with 3-wire PT100
Detect Voltage < 1V
Leakage
(alarm signal with S-1FP leak sensor)
Network Connection RJ45 jack connector
Output
+ 12V, 0.8A (max)
+ 24V, 1.0A (max)
Sensor HUB
One port limit 0.6A
Delta Bus + 12V, 0.8A (max)
Relay Outputs 26 Vdc (max), 0.8A (max)
Physical
Size (W x D x H) 440 x 157 x 44 mm
Weight 2.4 kg
Environmental
Operating Temperature 0 ~ 45°C
Storage Temperature - 20°C ~ 60°C
Operating Humidity 0 ~ 90% RH (non-condensing)
NOTE:
1. Refer to the rating label for the safety rating.
2. All specifications are subject to change without prior notice.