Chapter 5 : InsightPower SNMP IPv6 for EnviroStation Web
44
Analog Input
Formula: AI (Analog Input) 1 and AI2 are designed for general Analog
In-puts, each can be connected to a voltage (0~10Vdc) or current (0~20mA)
source. EnviroStation translates the ADC (Analog-to-digital converter) values
according to the following formula: (ADC-a)*b/c-d. You can select the unit
scale and define the unit string for the translated values.
Title: You can entitle devices for identification.
Warning / Alarm: You can set event type to Warning or Alarm.
RTD: The AI3 is designed to connect an RTD device. You can define the
conditions when reactions are triggered for Warning and Alarm levels.
Leakage: The AI4 is designed to connect a leakage sensor. You can select
the sensor sensitivity and Event Type.