EasyManuals Logo
Home>Delta>DC Drives>VFD185B43A

Delta VFD185B43A User Manual

Delta VFD185B43A
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #184 background imageLoading...
Page #184 background image
Chapter 7 Troubleshooting _VFD-B Series
7-2
Revision 10/2005, BE13, SW V4.08
7.2 Ground Fault
GFF
Ground fault
No
Yes
If output circuit(cable or
motor) of AC motor drive
is grounded?
Remove grounding
Maybe AC motor drive has
malfunction or misoperation
due to noise. Please
contact with DELTA.
7.3 Over Voltage (OV)
Over voltage
Yes
No
Yes
No
No
No
If voltage is within
specification
Reduce voltage to
be within spec.
If over-voltage is occurred without load
Maybe AC motor drive
has malfunction or
misoperation due to
noise. Please contact
with DELTA.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
When OV occurs, check if the
voltage of DC BUS is greater
than protection value
If OV occurs when
sudden acceleration
stops
Increase
deceleration
time
Increase setting time
Increase
acceleration
time
Reduce moment
of inertia
Reduce moment of load inertia
Use braking unit or DC braking
Need to check control method. Please contact with DELTA.
Need to considerate to
use braking unit and
DC braking

Table of Contents

Other manuals for Delta VFD185B43A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD185B43A and is the answer not in the manual?

Delta VFD185B43A Specifications

General IconGeneral
BrandDelta
ModelVFD185B43A
CategoryDC Drives
LanguageEnglish

Related product manuals