Chapter 7 Troubleshooting _VFD-B Series
Revision 10/2005, BE13, SW V4.08 7-3
7.4 Low Voltage (Lv)
Low voltage
Power cut, including momentary
power loss
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Restart after reset
Check if there is any malfunction
component in
power supply circuit
or disconnection
Change defective component
and check connection
Check if voltage is
within specification
Change power supply
system for requirement
Check if there is heavy load
with high start current in the
same power system
Check if Lv occurs when
breaker and magnetic
contactor is ON
Suitable
transformer
power
capacity
Check if voltage between +1/+2
and - is greater than
200VDC (for 230V models)
400VDC (for 460V models)
517VDC (for 575V models)
Maybe AC motor drive has malfunction.
Please contact with DELTA.
Control circuit has malfunction or
misoperation due to noise. Please
contact with DELTA.
Yes
Using the different power
supply for this drive and
heavy load system

Table of Contents

Other manuals for Delta VFD185B43A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD185B43A and is the answer not in the manual?

Delta VFD185B43A Specifications

General IconGeneral
BrandDelta
ModelVFD185B43A
CategoryDC Drives
LanguageEnglish

Related product manuals