Maintenance and Alarms
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 139
Table 12 lists ePDUand User alarms and events.
Table 12. ePDU and User Alarms and Events
Type Code
Identification and
Index Code Alarm or Event Description
2 201000 Dry Contact 1 Not Active The signal for Dry Contact 1 is active.
2 201100 Dry Contact 1 Active The signal for Dry Contact 1 is not active.
2 202000 Dry Contact 1 Open Dry Contact 1 is open.
2 202100 Dry Contact 1 Closed Dry Contact 1 is closed.
2 203000 Dry Contact 2 Not Active The signal for Dry Contact 2 is active.
2 203100 Dry Contact 2 Active The signal for Dry Contact 2 is not active.
2 204000 Dry Contact 2 Open Dry Contact 2 is open.
2 204100 Dry Contact 2 Closed Dry Contact 2 is closed.
2 205000 Sensor Probe Communication Failure Cleared Sensor Probe communication failure is cleared
2 205100 Sensor Probe Communication Failure Sensor probe communication failure detected
2 208000 Sensor Probe Not Connected Sensor probe not connected since firmware startup
2 208100 Sensor Probe Connected Sensor probe connected at least once since firmware
startup
2 206000 Humidity No Threshold No humidity threshold has been triggered.
2 206100 Humidity Warning Low Threshold The humidity level reading is less than the value
configured as the low humidity warning threshold.
2 206200 Humidity Critical Low Threshold The humidity level reading is less than the value
configured as the low humidity critical threshold.
2 206300 Humidity Warning High Threshold The humidity level reading is greater than the value
configured as the high humidity warning threshold.
2 206400 Humidity Critical High Threshold The humidity level reading is greater than the value
configured as the high humidity critical threshold.
2 207000 Temperature No Threshold No temperature threshold has been triggered.
2 207100 Temperature Warning Low Threshold The temperature level reading is less than the value
configured as the low temperature warning
threshold.
2 207200 Temperature Critical Low Threshold The temperature level reading is less than the value
configured as the low temperature critical threshold.
2 207300 Temperature Warning High Threshold The temperature level reading is greater than the
value configured as the high temperature warning
threshold.
2 207400 ePDU Temperature Critical High Threshold The temperature level reading is greater than the
value configured as the high temperature critical
threshold.
2 211000 ePDU Input 1 Current No Threshold No section current threshold has been triggered.
2 211100 ePDU Input 1 Low Current Warning The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2 211200 ePDU Input 1 Low Current Critical The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2 211300 ePDU Input 1 Over Current Warning The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.

Table of Contents

Other manuals for Eaton ePDU G3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton ePDU G3 and is the answer not in the manual?

Eaton ePDU G3 Specifications

General IconGeneral
BrandEaton
ModelePDU G3
CategoryPower distribution unit
LanguageEnglish

Related product manuals