D25
User's Manual
GE Grid Solutions
26
994-0081-3.00-21 GE Information
Graphic Display Panel (GDP) and Color GDP (CGDP) Overview,
Continued
What Can a
GDP/CGDP be
Used For?
The GDP/CGDP can eliminate the need for discrete substation devices.
For example, the GDP/CGDP can be used in place of the following devices:
circuit breaker control switch and semaphore
disconnector / earth switch and semaphore
ammeter, and ammeter selector switch
voltmeter, and voltmeter selector switch
MW meter
power factor meter
alarm annunciator panel
mimic diagram.
!
IMPORTANT
There are jumper settings at the back of the GDP/CGDP unit that are set at
the factory. These settings shall not be changed and any modification to them
may cause damage to the GDP/CGDP or other modules of the D25.
A D25 equipped with a GDP/CGDP has these limitations:
Only external status wetting can be used when the GDP/CGDP is installed.
the D25’s power supply field O/P is used exclusively to power the
GDP/CGDP.
connecting another external load to the field O/P will affect isolation, and
possibly overload the power supply.
The GDP/CGDP reduces the normal -20° to +70°C operational temperature
rating of the D25 to 0° to +50°C.
The 20-60 V
DC
D25 power supply is not available with the GDP/CGDP.