Configuring the D25 to work with a DNP3 I/O Module, continued
Example
Configuration
For example, when configuring your D25 RTU Master to work with a DNP
Digital Input Module, assume that you have a DNP Digital Input Module:
That is factory-configured with 64 digital inputs
That has DNP address 0032
• Which is to be polled every 500 ms.
• With every poll, we want a full status update.
To meet these requirements, you would configure the DNP DCA as shown in
the below table:
Table Parameter Value
Remote Device Table Application Address 0032
Remote Device Point
Mapping Table
DCA Object Type Binary Input
Number of Device Points 64
Remote Device Polling Table Poll Data Type Integrity
Poll Interval 500 ms