Chapter 3: Configuration and commissioning
28 Kilsen KFP-CF Series Installation Manual
• The zone delay configuration is set to allow delays in the zone reporting the fire
alarm. (This is the default configuration.)
If any of the above are not true, then the control panel overrides the configured delay
and activates the sounders immediately.
Fire routing delay
Use this menu to configure a fire routing delay of up to 10 minutes in operating
modes where the feature is available.
To configure a delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes quickly to indicate that the fire routing delay
configuration menu is active.
2. Select a delay value from 1 to 10 minutes using the value selection buttons (2
and 4).
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at access level 2.
To enable a configured delay:
1. Exit access level 3.
2. Enter the access level 2 password.
3. Press the Fire Routing Delay button.
A steady Fire Routing Delay LED indicates that the delay is enabled.
Default delays
The default fire routing delay for each operating mode is shown below.
Operating mode Default delay in minutes
EN 54-2 Scandinavia 01
NEN 2535 01
EN 54-2 00
EN 54-2 Evacuation
BS 5839-1
NBN S21-100
This feature is not available in these operating modes.