Appendix A: Configuration presets
60 Kilsen KFP-CF Series Installation Manual
Operating mode presets
EN 54-2
Configuration presets for EN 54-2 are as follows.
Two-zone control panels
Code Zone EOL Sounder outputs Zone type
01 Passive 2 Mixed
02 Passive, CleanMe
enabled
2 Mixed
Note: CleanMe is not currently available for Kilsen detectors.
Four- and eight-zone control panels
Code Zone EOL Sounder outputs Fire routing outputs
Zone type
01 Passive 3 1 Mixed
02 Passive, CleanMe
enabled
3 1 Mixed
Additional configuration characteristics are shown below.
Default sounder delay 0
Default fire routing delay 0
Default zone delay 0n
Start/Restart sounders Start sounders only if there is a fire alarm
Inputs and outputs are as follows.
INPUT1 Remote reset
INPUT2 Delays off
OUT1 Sounder circuit
OUT2 Sounder circuit
OUT3 Sounder circuit
OUT4 Fire routing
Note: Two-zone control panels have only two outputs (OUT1 and OUT2).