Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 33
Sounder re-sound
Use this menu to configure the sounder re-sound, on or off. This determines sounder
operation in a fire alarm event when sounders have been silenced by pressing the
Sounder Start/Stop button and a new alarm event is reported. The default setting is
ON.
To configure the sounder re-sound:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes quickly to indicate that the sounder re-sound
configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display Description
The sounders re-sound if a new fire alarm event is reported.
The sounders do not re-sound if a new fire alarm event is
reported.
Sounder synchronization
Use this menu to configure the sounder synchronization, on or off. This allows the
control panel to synchronize the activation of all sounders. The default setting is on.
To configure the synchronization:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes quickly to indicate that the sounder
synchronization configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.