Appendix A: Configuration presets
62 Kilsen KFP-CF Series Installation Manual
EN 54-2 Scandinavia
Configuration presets for EN 54-2 Scandinavia are as follows.
Two-zone control panels
Code Zone EOL Sounder outputs Zone type
07 Passive 2 Mixed
08 Passive, CleanMe
enabled
2 Mixed
Note: Note: CleanMe is not currently available for Kilsen detectors.
Four- and eight-zone control panels
Code Zone EOL Sounder outputs Fire routing outputs
Zone type
07 Passive 3 1 Mixed
08 Passive, CleanMe
enabled
3 1 Mixed
Additional configuration characteristics are shown below.
Default sounder delay 0
Default fire routing delay 0
Default extended fire routing
delay
0
Default zone delay 0n
Start/Restart sounders Start sounders or restart stopped sounders at access level 2 with or
without a fire alarm event
Inputs and outputs are as follows.
INPUT1 Fire routing delay / extended fire routing
delay
INPUT2 Delays off
OUT1 Sounder circuit
OUT2 Sounder circuit
OUT3 Sounder circuit
OUT4 Fire routing
Note: INPUT1 is not used on two-zone control panels. Two-zone control panels
have only two outputs (OUT1 and OUT2).