28 ADL500 • Quick installation guide - Specifications and connection
7.2.4 EMC guide line
In a domestic environment, this product may cause radio inference, in which case supplementary mitigation meas-
ures may be required.
The converters are protected in order to be used in industrial environments where, for immunity purposes, large
amounts of electromagnetic interference can occur. Proper installation practices will ensure safe and trouble-free
operation. If you encounter problems, follow the guidelines which follow.
- Check for all equipment in the cabinet are well grounded using short, thick grounding cable connected to a
common star point or busbar. Better solution is to use a conductive mounting plane and use that as EMC ground
reference plane.
- Flat conductors, for EMC grounding, are better than other type because they have lower impedance at higher
frequencies.
- Make sure that any control equipment (such as a PLC) connected to the inverter is connected to the same EMC
ground or star point as the inverter via a short thick link.
- Connect the return ground from the motors controlled by the drives directly to the ground connection (
) on the
associated inverter.
- Separate the control cables from the power cables as much as possible, using separate trunking, if necessary at
90º to each other.
- Whenever possible, use screened leads for the connections to the control circuitry
- Ensure that the contactors in the cubicle are suppressed, either with R-C suppressors for AC contactors or
󰀨
the contactors are controlled from the inverter relay.
- Use screened or armored cables for the motor connections and ground the screen at both ends using the cable
clamps.
- Use power shield kit to connect shield of motor cable to drive.
Note! For further information regarding electro-magnetic compatibility standards, according to Directive 2014/30/EU, conformity checks carried out on Gefran
appliances, connection of filters and mains inductors, shielding of cables, ground connections, etc., consult the “Electro-magnetic compatibility guide”
(1S5E84) you can download from www.gefran.com.
7.2.5 Block diagram of power section
ADL5.0.-...-F-..), an AC/DC converter, a system for pre-loading
DC capacitors, a DC/AC converter, a power supply unit and an integrated braking unit.
 between terminals BR1 and BR2.
An optional external BUy braking unit can be used and connected to terminals C and D. Refer to the BUy handbook for
further information.
To manage emergency situations (drive power failure) the unit also envisages ordering the option with an emergency
module inside the drive (ADL5.0.-...-EMS models) and powering the emergency unit between terminals EM and D with
a battery.
Sizes 1040 ... 2150
RELAY
DC LINK+
DC LINK-
SMPS
C
BR1 BR2
D EM
U
V
W
C1
L1
L2
L3
EMS CARD
(*)
(*)
(*)
(*)
(*)
(*) On ADL5.0-...-EMS only
Warning!
Attention

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADL510 and is the answer not in the manual?

gefran ADL510 Specifications

General IconGeneral
Brandgefran
ModelADL510
CategoryInverter
LanguageEnglish

Related product manuals