GREE GMV5 INDOOR UNIT SERVICE MANUAL
126
probably not be dealt with on time because of the inconvenience of the business contact.
It should be guided under the professional personnel when the air conditioner unit is moved to
other place.
Installation of the unit must be in accordance with National Electric Codes and local regulations.
Improper installation will affect unit’s performance, so do not install the unit by yourself. Please
contact local dealer to arrange professional technicians for the installation.
Do not connect power until all installation work is finished.
The height of ex-factory supporter is 120mm. If user wants to increase or decrease unit
installation height, please purchase the supporter of different height. Other height of supporter
is 80mm, or 160mm.
Default height of inlet grille is 120mm. If the supporter of 80mm or 160mm high is selected,
please change the height of inlet grille to 80mm or 160mm accordingly.
3.15.4 Selection of air switch and power cord
Model
Power Cord Size
Air Switch apacity
(A)
Minimum Sectional
Area of Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power Cord
(mm
2
/AWG)
GMV-ND22ZA/A-T
220-240V/50Hz
208-230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND28ZA/A-T
220-240V/50Hz
208-230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND36ZA/A-T
220-240V/50Hz
208-230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND45ZA/A-T
220-240V/50Hz
208-230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND56ZA/A-T
220-240V/50Hz
208-230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND63ZA/A-T
220-240V/50Hz
208-230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND71ZA/A-T
220-240V/50Hz
208-230V/60Hz
6
1.0/AWG18
1.0/AWG18
4 Installation of drain pipe
4.1 Precautions When Doing the Piping Work
(1) It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines which
are likely to produce corrosive or peculiar smell to prevent the smell from entering indoors or
corrupt the unit.
(2) It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water from
pouring in and cause property loss or personal injury.
(3) Condensate drain pipe should be connected into special drain system for air conditioner.

Table of Contents

Other manuals for Gree GMV-ND22C/A-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-ND22C/A-T and is the answer not in the manual?

Gree GMV-ND22C/A-T Specifications

General IconGeneral
BrandGree
ModelGMV-ND22C/A-T
CategoryAir Conditioner
LanguageEnglish

Related product manuals