GREE GMV5 INDOOR UNIT SERVICE MANUAL
74
5.2 Engineering Application Functions Operated through the
XK49 Wired Controller
XK49 Wired Controller
5.2.1 Master IDU Settings
Method 1: In power-off status, press and hold the MODE button for five seconds to set the IDU
connected with the current wired controller to master IDU. If the setting is successful, MASTER will be
on.
Method 2:
Step 1: In power-on or power-off status, press and hold the MODE button and SWING
simultaneously for five seconds to enter the parameter query interface.
Step 2: In C00 status, press and hold the MODE button and SWING simultaneously for five
seconds to enter the parameter setting interface.
Step 3: Press “▲” or “▼” to switch level 2 parameter codes till P10 is displayed on the temperature
area.
Step 4: Press the MODE button to set the parameter to 01 and then Press the ENTER button.
If the setting is successful, MASTER on the wired controller will be on.
GREE
MASTER
SWING FAN MODE
5.2.2 User Parameter Query
User parameters can be queried in power-on or power-off status.
MASTER
图标

Table of Contents

Other manuals for Gree GMV-ND22C/A-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-ND22C/A-T and is the answer not in the manual?

Gree GMV-ND22C/A-T Specifications

General IconGeneral
BrandGree
ModelGMV-ND22C/A-T
CategoryAir Conditioner
LanguageEnglish

Related product manuals