EXCEL 50 MMI - USER GUIDE
EN2B-0222GE51 R0216 18
Fig. 21. Deleting a daycycle
New daycycles are created by copying and modifying existent daycycles.
To copy and modify an existent daycycle, go to Fig. 17 (see page 15), move the
cursor to the daycycle to be copied (e.g. DP_1), press the PLUS key, and confirm
the query appearing in the resultant screen (see Fig. 22). If desired, you can reject
the query using the CANCEL key.
Fig. 22. Creating a daycycle
The copy of the new daycycle is issued the name "DP" to which the lowest
number which has not already been assigned to an existent daycycle will be
appended. Thus, the first new daycycle to be created would be named DP_1.
NOTE: If the "COPY" function is used to create a new daycycle, the next free
daycycle will be assigned. This means that the default daycycle can be
overridden by a new daycycle.
Deleting a Switch-Point
Existent switch-points can be deleted.
To do this, go to the listbox displayed in Fig. 18 (see page 16), move the cursor to
the switch-point to be deleted, press the MINUS key, and confirm the query
appearing in the resultant screen (see Fig. 23). If desired, you can reject the query
using the CANCEL key.

Table of Contents

Other manuals for Honeywell Excel 50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel 50 and is the answer not in the manual?

Honeywell Excel 50 Specifications

General IconGeneral
BrandHoneywell
ModelExcel 50
CategoryController
LanguageEnglish

Related product manuals