EasyManua.ls Logo

Inovance MD310 T2.2B User Manual

Inovance MD310 T2.2B
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
5 Parameter Table
- 27 -
5 Parameter Table
5�1 General Parameters
Group F0: Standard Parameters
Para� No� Para� Name Setting Range Unit Default Commission
F0-01 Motor 1 control mode 0: Sensorless vector control (SVC)
2: Voltage/Frequency control (V/F)
N�A� 2
F0-02 Command source
selection
0 to 2 N�A� 0
F0-03 Main frequency source
X selection
0 to 9 N�A� 0
F0-04 Auxiliary frequency
source Y selection
The same as F0-03 (Main frequency source
X selection)
N�A� 0
F0-05 Range base of auxiliary
frequency Y for X and Y
operation superposition
0: Relative to max� frequency
1: Relative to main frequency X
N�A� 0
F0-06 Range of auxiliary
frequency Y for X and Y
operation superposition
0 to150 % 100
F0-07 Frequency source
superposition selection
00 to 34 N�A� 00
F0-08 Preset frequency 0�00 to max frequency (F0-10) N�A� 50�00
F0-09 Rotation direction 0: Same direction
1: Reverse direction
N�A� 0
F0-10 Max� frequency 50�00 to 600�00 Hz 50�00
F0-11 Source of frequency
upper limit
0 to 5 N�A� 0
F0-12 Frequency upper limit Frequency lower limit (F0-14) to max�
frequency (F0-10)
Hz 50�00
F0-13 Frequency upper limit
offset
0�00 to max frequency (F0-10) Hz 0�00
F0-14 Frequency lower limit 0�00 to frequency upper limit (F0-12) Hz 0�00
F0-15 Carrier frequency 0�8 to 16�0 kHz Model
dependent
F0-16 Carrier frequency
adjustment with
temperature
0: No
1: Yes
N�A� 1
F0-17 Acceleration time 1 0�00 to 650�00 (if F0-19 = 2)
0�0 to 6500�0 (if F0-19 = 1)
0 to 65000 (if F0-19 = 0)
s Model
dependent
F0-18 Deceleration time 1 0�00 to 650�00 (if F0-19 = 2)
0�0 to 6500�0 (if F0-19 = 1)
0 to 65000 (if F0-19 = 0)
s Model
dependent
F0-19 Acceleration/
Deceleration time unit
0: 1
1: 0�1
2: 0�01
s 1
F0-21 Frequency offset of
auxiliary frequency
source for X and Y
operation superposition
0�00 to max frequency (F0-10) Hz 0�00
F0-22 Reserved - - -

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Inovance MD310 T2.2B and is the answer not in the manual?

Inovance MD310 T2.2B Specifications

General IconGeneral
Rated Power2.2 kW
Control ModeV/F control, Sensorless vector control (SVC)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Short circuit
Communication InterfaceModbus RTU
Humidity5% to 95% (non-condensing)
AltitudeBelow 1000m (derating above 1000m)
Operating Temperature-10°C to +40°C (derating above 40°C)

Related product manuals