5 Parameter Table
- 42 -
Group FD: Communication
Para� No� Para� Name Setting Range Unit Default Commission
FD-00 Baud rate 0000 to 9999 N�A� 5005
FD-01 Data format symbol 0 to 3 N�A� 0
FD-02 Local address 0: Broadcast address;
1 to 247
N�A� 1
FD-03 Response delay 0 to 20 ms 2
FD-04 Communication timeout 0�0 (invalid);
0�1 to 60�0
s 0�0
FD-05 Communication protocol 30, 31 N�A� 31
FD-06 Current resolution read by
communication
0: 0�01
1: 0�1
A 0
FD-07 Factory reserved 0: Background software invalid
1: Background software valid
N�A� 0
FD-08 Extension card communication
timeout time
0�0: Invalid
0�1 to 60�0
s 0�0