5 Parameter Table
- 34 -
■
Group F7: Keypad Control And LED Display
Para� No� Para� Name Setting Range Unit Default Commission
F7-01 MF�K Key function selection 0 to 5 N�A� 5
F7-02 STOP/RESET key function 0 to 1 N�A� 1
F7-03 LED display running
parameters 1
0000 to FFFF N�A� 1F
F7-04 LED display running
parameters 2
0000 to FFFF N�A� 0
F7-05 LED display stop
parameters
0000 to FFFF N�A� 33
F7-06 Load speed display
coefcient
0�0001 to 6�5000 N�A� 1�0000
F7-07 Heatsink temperature of
inverter module
0 to 100 °C -
F7-08 Product number N�A� N�A� N�A�
F7-09 Accumulative running time 0 to 65535 h N�A�
F7-10 Performance software
version
N�A� N�A� N�A�
F7-11 Functional software version N�A� N�A� N�A�
F7-12 Number of decimal places
for load speed display
Number of decimal places
for U0-19/U0-29
1: 1 decimal place
2: 2 decimal places
Number of decimal places
for U0-14
0: 0 decimal place
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
N�A� 21
F7-13 Accumulative power-on
time
0 to 65535 h N�A�
F7-14 Accumulative power
consumption
0 to 65535 kWh N�A�
F7-15 Temporary performance
software version
N�A� N�A� N�A�
F7-16 Temporary functional
software version
N�A� N�A� N�A�