5 Parameter Table
- 30 -
Group F3: V/F Control
Para� No� Para� Name Setting Range Unit Default Commission
F3-00 V/F curve setting 0 to 9 N�A� 0
F3-01 Torque boost 0�0 to 30�0 % 0�0
F3-02 Cut-off frequency of torque
boost
0�00 to max output frequency Hz 50�00
F3-03 Multi-point V/F frequency 1
(F1)
0�00 to F3-05 Hz 0�00
F3-04 Multi-point V/F voltage 1 0�0 to 100�0 % 0�0
F3-05 Multi-point V/F frequency 2 F3-03 to F3-07 Hz 0�00
F3-06 Multi-point V/F voltage 2 0�0 to 100�0 % 0�0
F3-07 Multi-point V/F frequency 3 F3-05 to rated motor frequency (F1-04) Hz 0�00
F3-08 Multi-point V/F voltage 3 0�0 to 100�0 % 0�0
F3-09 V/F slip compensation gain 0 to 200�0 % 0�0
F3-10 V/F over-excitation gain 0 to 200 % 64
F3-11 V/F oscillation suppression
gain
0 to100 % Model
dependent
F3-12 Oscillation suppression
mode selection
0 to 4 N�A� 3
F3-13 Voltage source for V/F
separation
0 to 8 N�A� 0
F3-14 Voltage digital setting for V/
F separation
0 to rated motor voltage V 0
F3-15 Voltage rise time of V/F
separation
0�0 to 1000�0 s 0�0
F3-16 Voltage decline time of V/F
separation
0�0 to 1000�0 s 0�0
F3-17 Stop mode selection for
V/F separation
0: Frequency and voltage declining to 0
independently
1: Frequency declining after voltage declining
to 0
N�A� 0
F3-18 Current limit level 50 to 200 % 150
F3-19 Current limit selection 0: Disabled
1: Enabled
N�A� 1
F3-20 Current limit gain 0 to 100 N�A� 20
F3-21 Compensation factor of
speed multiplying current
limit level
0 to 200 % 50
F3-22 Voltage limit 200�0 to 810�0 V 760�0
F3-23 Voltage limit selection 0: Disabled
1: Enabled
N�A� 1
F3-24 Frequency gain for voltage
limit
0 to 100 N�A� 30
F3-25 Voltage gain for voltage
limit
0 to 100 N�A� 30
F3-26 Frequency rise threshold
during voltage limit
0 to 50 Hz 5
F3-27 Slip compensation time
constant
0�1 to 10�0 s 0�5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD310 T2.2B and is the answer not in the manual?

Inovance MD310 T2.2B Specifications

General IconGeneral
Rated Power2.2 kW
Control ModeV/F control, Sensorless vector control (SVC)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Short circuit
Communication InterfaceModbus RTU
Humidity5% to 95% (non-condensing)
AltitudeBelow 1000m (derating above 1000m)
Operating Temperature-10°C to +40°C (derating above 40°C)