28 xGen Installation & Programming Guide
EN50131-3 Compliancy
In order to be compliant with the technical specification EN50131-3 (Alarm
systems – Control and indicating equipment), the following guidelines must be
taken into account:
The tamper of the warning device should be connected to a 24 hour zone
input.
Overriding is not supported with xGen. In case a zone is faulted, one shall
bypass the zone manually before arming or verify the zone and clear the fault.
See user instructions
Hold-up zones are not allowed to be set for bypass
Zone isolation is not supported
Options affected by EN 50131 regulations
EN 50131 Grade 2 Required settings
The following options and values are mandatory for EN 50131-1 Grade 2
regulations.
Period, 24 h for every path to meet ATS Class 2, 4 h for the IP path to meet
Class 4.
View Partitions and 2.2.1.n.3.4 Control Partitions settings are identical
Buzzer silent, never
• Quick set, off
Function keys, all set to None
User group options, 25. No OP/CL reports option set to No
Inhibit, set to No for all zones with type 5. Panic, 6. 24H
Swinger shunt, set to Yes for all zones
ACK on keypad, set to None for all zones with type 9. Keyswitch
Entry time, 45 s maximum
Entry alarms, Instant
Active, set to No for all schedules.
Activation, internal and external siren 90 to 900 s
Delay time, external siren 600 s maximum
Armed display, 30 s maximum
Mains reporting delay, 3600 s maximum
User code required, enabled
Armed display, always
• Alarm list, disabled