xGen Installation & Programming Guide 29
• Inhibit includes, all allowed except engineer reset, which must be disabled
• Pending alarms, enabled
• Swinger shunt ≥ 3
• Report restore, on ACK
• Line fault, enabled per path used
• Line fault delay, 0 s
• Refer to xGen Reference Manual for additional features, accessible at level 3
It is required to apply the following supervision settings for wireless expanders:
• Short supervision: 20 minutes
• Long supervision: 2 hours
• Smoke supervision: 4 hours
Caution: When any option, any additional function or any additional zone type in
this section does not comply with the EN 50131 requirements, the EN 50131
Grade 2 label must be removed from the system.
Optional Functions
• Detection of storage device – Failure
• Detection of low output voltage
EN 50131 compliance precautions
Installation
In order to install an EN 50131 compliant system, please make sure that all
system components are EN 50131 compliant.
Programming
Make sure that all system settings are in line with regulatory compliance
guidelines.
Size of log / event history
For full EN 50131 Grade 3 compliance, the system must store at least 500
events.
Marking
It is only allowed to mark the system with the EN 50131 Grade 2 label, if the
following requirements are met:
• All system components are EN 50131 compliant.
• All settings are done according to “EN 50131 Grade 2” on page 28.
If any of these two items is not valid, the EN 50131 Grade 2 label must be
removed from the system.