45
ANTRIEBSTECHNIK
COMBIVERT F0
6.4 Protection - Parameter
Die Protection-Parameter schützen den Frequenzumrichter vor
Überlastungen und Störungen.
6.4 Protection Parameter
The Protection Parameters protect the frequency inverter against
overloads and interferences.
Stromgrenze / Pegel
Die Stromgrenze schützt den Umrichter gegen Abschal-
ten durch Überstrom während konstanter Drehzahl. Mit
dem Pegel wird die Stromgrenze festgelegt, ab der die
Funktion aktiv werden soll.
Einstellbereich: 10…150 %, OFF
(Stall-Funktion siehe Anhang A.1)
Stall prevention level
The stall prevention level protects the inverter against
switch-off caused by overcurrent during constant speed.
With the stall prevention level the current limit is
determined at which the function shall become active.
Adjustment range: 10…150 %, OFF
(Stall Function see Annex A.1)
Stromgrenze / Rampenzeit
Wird der eingestellte Stromgrenz-Pegel überschritten,
wird die Frequenz, je nach M-n-Charakteristik (P.2),
erhöht bzw. erniedrigt. Die ACC-/DEC-Zeiten können
mit diesem Parameter unabhängig von den normalen
ACC-/DEC-Rampen im Bereich von 0.05…650 s einge-
stellt werden. Der eingestellte Wert bezieht sich auf
0…Sollwertmaximum (o.2).
ACC / DEC time during stall prevention
If the adjusted stall prevention level is exceeded the
frequency is increased or decreased according to the
stall torque characteristic (P.2). With this parameter the
ACC/DEC times can be adjusted in the range of
0.05…650 s, independent of the regular ACC / DEC
ramps. The adjusted value refers to 0… set point value
maximum (o.2).
P.0 : Stall prevention level
P.1 : ACC / DEC time during stall
prevention
P.2 : Stall torque characteristic
P.3 : LAD stop load level
P.4 : U/f - function
P.6 : Speed search condition
P.7 : Automatic retry UP
P.11 : Energy - saving mode
P.12 : Energy - saving level
P.13 : LAD stop condition
P.14 : LD stop DC voltage level
P.15 : Load-dependent set shifting level
P.21 : OH switch-off time
P.0 : Stromgrenze / Pegel
P.1 : Stromgrenze / Rampenzeit
P.2 : Stromgrenze / M-n-Charakteristik
P.3 : Rampenstop / Strompegel
P.4 : U/f-Funktion
P.6 : Drehzahlsuche / Aktivierung
P.7 : Auto-Reset UP
P.11 : Energiesparfunktion / Aktivierung
P.12 : Energiesparfunktion / Pegel
P.13 : Rampenstop / Aktivierung
P.14 : Verzögerungsstop /
DC-Spannungspegel
P.15 : Lastabhängige Satzumschaltung /
Pegel
P.21 : OH-Abschaltzeit