EasyManuals Logo
Home>Kohler>Portable Generator>Power Systems 8RESV

Kohler Power Systems 8RESV User Manual

Kohler Power Systems 8RESV
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
TP-6881 7/15 17Section 2 Scheduled Maintenance
2.1.1 Service Schedule
System Component or Procedure
See
Section
Visually
Inspect
Check Change Clean Test
Frequency
Fuel
Flexible lines and connections X R Quarterly
Main tank supply level X Weekly
Fuel piping X Yearly
Lubrication
2.2
Oil level
X X
8 hours or
before use
Crankcase breather hose X Yearly or 500 hours
Change oil X Yearly or 100 hours
Replace filter X Yearly or 100 hours
Cooling
2.5
Air ducts, louvers X X Yearly
Exhaust Line
2.6
Leakage X X Weekly
Insulation, fire hazards X Yearly
Obstructions or combustible materials near exhaust
outlet
X Weekly
DC Electrical System
2.9
Battery charger operation, charge rate (if equipped) X Monthly
Remove corrosion, clean and dry battery and rack X X Yearly
Clean and tighten battery terminals and inspect
boots
X X Yearly
Battery electrolyte level and specific gravity * X Yearly
AC Electrical System
Tighten control and power wiring connections X Yearly
Remote control system, if equipped X Monthly
Visible wear or damage X Quarterly
Wire abrasions where subject to motion X X Six Months
Wire-cable insulation condition X 3 Years or 500 hours
Engine and Mounting
Visible wear or damage X Weekly
Air cleaner service [
2.4
150 300
Yearly or hours
shown
Spark plugs (apply anti-seize lubricant for easy
removal)
2.3
X Yearly or 500 hours
Checked/adjusted valve lash, 8RESV(L) Engine
SM
D 100 hours
Checked/adjusted valve lash, 10/12RESV(L) Engine
SM
D 500 hours
Replace stepper motor coupling and bushing D 500 hours
Generator
Visible wear or damage X Quarterly
Exercise generator set X Weekly
Measure and record resistance readings of
windings with insulation tester (Meggerr,with
SCR assembly or rectifier and load leads
disconnected) *
D 3 Years
General Condition of Equipment
Evidence of vibration, leakage, excessive noise,
temperature, or deterioration
X X X Weekly
Interior of sound enclosure X X Quarterly
* Not necessary for maintenance-free batteries.
[ Service more frequently under extremely dusty/dirty conditions.
Meggerr is a registered trademark of Biddle Instruments.
XAction
D Authorized distributor/dealer only
R Replace as necessary

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Power Systems 8RESV and is the answer not in the manual?

Kohler Power Systems 8RESV Specifications

General IconGeneral
BrandKohler
ModelPower Systems 8RESV
CategoryPortable Generator
LanguageEnglish

Related product manuals