106 DAA2 & DAX — P/N 53265:A1 8/24/2011
DAA Digital Audio Amplifiers Installation
Connect all DAAs sharing a set of batteries directly to the batteries using 12 AWG. If the batteries
are located outside of the DAA cabinet, the wiring must be in conduit that is no greater than 20 ft.
(6.09 m) long.
Figure C.14 Four DAAs Sharing 55AH Batteries
CPS-24tb3batshare.wmf
If batteries are not in the same cabinet
as the DAA2s, wiring must be in conduit
that is 20 ft. (6.09 m) long or less.
DAA2 1
TB3 on CPS-24
SW1 must be set
to “Disable” on all
but one of these
DAA2s. VeriFire
programming
must indicate
which are
enabled/disabled.
DAA2 2
TB3 on CPS-24
DAA2 3
TB3 on CPS-24
DAA2 4
TB3 on CPS-24