DAA2 & DAX — P/N 53265:A1 8/24/2011 15
Description DAA2 Digital Audio Amplifiers
Charger voltage: 27.6 VDC.
For battery calculation worksheet and standby operating times, refer to Appendix B.1, “DAA2
Battery Calculations”, on page 84.
Utilizes wire sizes 12-18 AWG..
When AC power is lost, the deeply-discharged battery cutoff protection will be invoked at 17
volts. The power supply will be disconnected from the batteries. The power supply’s normal
operation will be restored when AC power returns.
DAA2-5025/70 and DAA2-7525 Boards
Wire Digital Audio Ports A and B - TB2, TB3
Refer to the Wiring Guide, p/n 52916ADD, for acceptable wire types.
EIA-485 format.
Power-limited and supervised.
Refer to Section 5, “Fiber Option Modules”, on page 75 for fiber connection information.
When a fiber option module is mounted on a DAA2, it disables the corresponding wire
terminals. TB2 (Digital Audio Port A) is disabled when a fiber option board is connected at J9.
TB3 (Digital Audio Port B) is disabled when a fiber option board is connected at J10.
Alarm Bus - TB4
Power-limited and supervised by source.
Recommended wiring: 14-18 AWG twisted-pair.
Requires 16VDC minimum @ 20mA across the terminals to activate. Nominal 24 VDC.
Remote Microphone Interface - TB5
RMI Power - +24VDC, power-limited @ 100mA.
Recommended wiring: 14-18 AWG twisted-pair, Max. 14 AWG.
Nominal AC signal strength 2.5V
RMS
, 3V
RMS
Max.
Power-limited.
Supervised.
Max. distance between remote microphone and DAA2: 1000 ft (304.8 m).
FFT Riser - TB7
Power-limited output.
Supervised.
Class A or Class B operation.
Class B 2-wire connections require a 3.9k ohm 1/2 watt resistor (P/N R-3.9K).
Max. wiring resistance (including individual telephone zone to last handset) permitted is 50
ohms, 10,000 ft (3048 m) max. wiring distance at 14 AWG to last handset.
DAA2-5025 w/ BDA in Group 2 of VeriFire
Tools programming*
DAA2-5070 w/ BDA in Group 2 of VeriFire
Tools programming*
No
No
No
No
No
No
* Refer to “DAA2-50 Configurations with BDA” on page 72 for further explanation.
Charge
Batteries Less
Than 26AH
Charge
26AH to <
50AH
Batteries
Charge
50AH to
200AH
Batteries
Table 2.2 Battery Charging Capabilities
NOTE: A 50 watt DAA2 with 2 groups will have its charger disabled automatically. Groups are
explained in the Audio Groups appendix of the DVC Digital Voice Command manual.