78 DAA2 & DAX — P/N 53265:A1 8/24/2011
Fiber Option Modules Installation
5.3.3 Single- or Multi-mode DVC (DVC-PCB or less) or DAA
Installation
Single-mode
A DS-SFM must be used to connect a DAA2 or DAX to a single-mode fiber DVC or DAA.
Figure 5.4 Single-mode Fiber DVC or DAA Installation
Multi-mode
A DS-RFM must be used to connect a DAA2 or DAX to a multi-mode fiber DVC or DAA.
Figure 5.5 Multi-mode Fiber DVC or DAA Installation
DAX (or DAA2)
DS-SFM
Single-mode
Fiber DAL Cable
Single-mode Fiber
DVC (or single-
mode fiber DAA)
ST* Style
Connections
LC Style
Connections
*ST® Style (ST is a registered
trademark of AT&T)
12dB min
17dB max
0dB min
4dB max
RX
TX
DAX (or DAA2)
DS-RFM
Multi-mode
Fiber DAL Cable
Multi-mode Fiber
DVC (or multi-mode
fiber DAA)
ST
®
Style*
Connections
LC Style
Connections
*ST® Style (ST is a registered
trademark of AT&T)
0dB min
2dB or 4dB max
12dB min
16dB max
RX
TX