EasyManuals Logo
Home>Notifier>Amplifier>DAX

Notifier DAX User Manual

Notifier DAX
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #119 background imageLoading...
Page #119 background image
DAA2 & DAX — P/N 53265:A1 8/24/2011 119
Installation DAA Digital Audio Amplifiers
A backup amplifier can support one failed primary amplifier at a time. Should another primary
amplifier also fail, the backup amplifier may also fail, generating an AMPLIFIER LIMIT trouble
until the load is reduced or reset.
Figure C.32 One-to-Many Backup
UL Power-limited Wiring Requirements
Power-limited and non-power-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25 inches (6.35 mm) from any non-power-
limited circuit wiring. All power-limited and non-power-limited circuit wiring must enter and exit
the cabinet through different knockouts and/or conduits.
Figure C.33 Typical Backbox Wiring
Primary DAA 1 Primary DAA 2 Primary DAA 32
DAABRDtb10.wmf
From “Out”
terminals
on backup
amplifier
To
Speakers
To
Speakers
To
Speakers
Power-limited
circuits
Non-power-limited
circuits
DAAULwiring.wmf

Table of Contents