DAA2 & DAX — P/N 53265:A1 8/24/2011 81
DAA2 Current Draw Calculations AC Current Draw Calculations
DAA2-7525
Application
120V 50/60Hz
4.68A max.
220-240V 50/60Hz
2.68A max.
AC
Draw
A
Calculation for
when amplifier
is active
B
Calculation for
when amplifier
is not active
AC
Draw
C
Calculation for
when amplifier
is active
D
Calculation for
when amplifier
is not active
Basic draw 0.54 0.54 0.54 0.32 0.32 0.32
Used as a primary amplifier* 2.28 + 2.28 1.34 + 1.34
Charger - less than 26AH** 0.79 +______ +______ 0.58 +______ +______
Charger - 26AH to less than 50AH** 1.49 +______ 0.87 +______
BDA as a backup or 2nd channel in Audio Group 1. 0.10 +______ +______ 0.06 +______ +______
AUX power (on CPS-24) 0.39 +______ +______ 0.21 +______ +______
AC Draw Totals =______ =______ or =______ =______
The highest total of column A
and column B must be <
the
maximum AC current draw
allowed of 4.68A.
The highest total of column C
and column D must be <
the
maximum AC current draw
allowed of 2.68A.
* A DAA2-7525 used as a backup will draw the same power as a primary when it is active.
** When the amplifier is active, the column A charger entry must be 0.79 or the column C entry must be 0.58, no matter what size the charger is.
Table A.3 AC Draw Worksheet for DAA2-7525