Step Run and Break Section 4-3
109
Condition Combination
The I/O break condition expression can be set by combining conditions (Turn
on check boxes for conditions registered in AND LIST or OR LIST). The I/O
break condition expression is configured by combining [AND LIST] (Condi-
tions are combined with AND operators) and [OR LIST] (Conditions are com-
bined with OR operators) with logical operators (AND/OR). The relationship
between [AND LIST] and [OR LIST] is expressed by the following logic ex-
pression.
( [AND LIST] ) AND ( [OR LIST] )
A maximum of 64 items can be registered in AND LIST and OR LIST respec-
tively. Also, a maximum of 64 combinations of logic expressions can be cre-
ated for both the lists together.
I/O break condition setting
expression
(IO0.0=ON and H1.15=ON) and
(DM0>=#7FFF or A401.08=ON)