EasyManuals Logo
Home>Omron>Touch terminals>NT20S

Omron NT20S User Manual

Omron NT20S
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
57
Connection to a PC by the NT Link (1:N)
Section 2-6
2-6-3 PC Switch Settings
When the PC and NT20S units have been connected, set the switches at the CPU
module at the PC side in order to enable communication using the NT link method.
S C series, C200HX/HG/HE
Write the communication conditions directly to the “PC system area” (data
memory) using a peripheral tool (e.g., SYSMAC support software). For details on
the operation for setting the “PC system area”, refer to the “SYSMAC C200HX/
HG/HE Installation Guide” (W302-E1-j).
[PC system setting area setting]
With C200HX/HG/HE, the setting area differs according to which port among the
standard port of the CPU unit and the port of the expansion communication board
is used for the connection.
Port Channel # Writing Value Settings
C200HX/HG/HE
RS-232C port
DM6645
Use NT link (1:N)
=
C200HX/HG/HE
port A
DM6555
5j00
=
.
in the maximum
number of connect-
C200HX/HG/HE
port B
DM6550
able PTs (1 to 7). (
)
(
) When using C200HE, the PT unit No. range is 1 to 3.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NT20S and is the answer not in the manual?

Omron NT20S Specifications

General IconGeneral
BrandOmron
ModelNT20S
CategoryTouch terminals
LanguageEnglish

Related product manuals