135
Communications Timing Section 4-4
Command transmission to the host computer can start even when the port is
receiving a command from the host computer (1). The transmission of a
response to the command from the host computer is postponed until the
transmission of the command to the host computer is completed (2).
When a response is not required from the host computer, the Communica-
tions Port Enabled Flag will turn ON when the command to the host computer
has passed from the CPU Unit to the port.
Host Computer Receiving Data
At (1) in the diagram, the response to a command sent from the host com-
puter is being transmitted from the port. In this case, the command transmis-
sion to the host computer is postponed until the response transmission is
completed (2).
When a response is not required from the host computer, the Communica-
tions Port Enabled Flag will turn ON when the command to the host computer
has passed from the CPU Unit to the port.
Response Required
Host computer
Command
Command
Response
Response
Serial Communications
Board/Unit
Communications Port Enabled Flag
Command acknowledged
Command completed
No Response Required
Host computer
Serial Communications
Board/Unit
Command
Command
Response
Communications Port Enabled Flag
Command acknowled
g
ed
Command completed
(1) (2)
(1)
(2)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS1W-SCB41-V1 and is the answer not in the manual?

Omron SYSMAC CS1W-SCB41-V1 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS1W-SCB41-V1
CategoryNetwork Hardware
LanguageEnglish

Related product manuals